ConnectLinks

← All products

Evaluation units available

Lite range · CL-B-D-S-2

Modbus-to-BACnet Bridge Lite

Reads Modbus RTU and Modbus TCP devices and presents them to your BMS as native BACnet/IP objects it can read, subscribe to and command. No custom driver, no cloud, no web page.

Download the brochure (PDF)Request an evaluation unit

Choose this whenModbus meters, drives, chillers or gensets must appear in your building management system.
Connects toUp to 32 Modbus RTU devices on 2 × RS-485, plus 5 Modbus TCP devices
Data leaves viaNone — BACnet/IP server on the LAN only
Capacity37 devices · 500 BACnet points (design target)
Order codeCL-B-D-S-2

What it does

The bridge turns Modbus registers into named BACnet objects (analog, binary and multi-state inputs, outputs and values) with scaling, byte order and 15 data types. Each meter gets its own block of object numbers and a name prefix, so the BMS point list reads like the plant.

Typical sites: panel builders · chillers and gensets · energy metering · UPS and drives · BMS retrofits.

Writes the BACnet way

Commandable outputs carry a full 16-level priority array and a relinquish default, so your BMS commands plant the way it expects to. Change-of-value subscriptions are supported.

Faults the BMS can see

When a meter stops answering, its points show FAULT and a communication failure instead of a frozen value, and each meter has its own health point.

Commissioned from a spreadsheet

Load a full point list in one step from CSV; a list with an error is refused whole. EDE export for the BMS. The bridge stays silent on BACnet until it is commissioned.

Standards

BACnet/IP server to the B-GW profile, protocol revision 28. Built and self-tested to the BTL Test Package; not BTL-listed. PICS on request.

Evaluation units are available. An evaluation unit runs with every feature for 30 days and becomes permanent with a per-unit key, with no reflash. Specifications are preliminary and may change. Request a unit or a quotation.